| Residential split air conditioner | 208–240 V AC | Single-phase | 2 poles | 24 V AC is common; confirm the control voltage | Compressor and condenser-fan motor rated-load current, locked-rotor current, and motor horsepower | Two-pole definite-purpose contactor with voltage and motor ratings meeting or exceeding the nameplate requirements | Both ungrounded supply conductors are normally switched. The equipment grounding conductor must not be switched. |
| Residential heat pump | 208–240 V AC | Single-phase | 2 poles; additional contacts may be required for auxiliary functions | 24 V AC is common; verify the control-board specification | Compressor, outdoor fan, defrost operation, auxiliary heat, and nameplate current values | Two-pole compressor contactor sized for the heat-pump compressor and outdoor fan; use separate switching devices where the design requires them | Do not assume a standard cooling-only control sequence. Defrost and auxiliary-heat circuits may require separate relays or contactors. |
| Three-phase commercial condensing unit | 208–230 V AC or 460–480 V AC | Three-phase | 3 poles | 24 V AC, 120 V AC, or another control voltage depending on the unit | Compressor full-load current, locked-rotor current, motor horsepower, system voltage, and phase sequence | Three-pole contactor with a voltage rating suitable for the system and motor-duty ratings equal to or greater than the equipment requirements | Confirm the contactor is suitable for three-phase motor switching. Check rotation after installation if the compressor or fan is phase-sensitive. |
| Packaged rooftop air-conditioning unit | 208–230 V AC or 460–480 V AC | Single-phase or three-phase | 2 poles for single-phase; 3 poles for three-phase | 24 V AC is common; some controls use line-voltage coils | Compressor and supply/outdoor fan motor loads, minimum circuit ampacity, and maximum overcurrent protection | Select the pole count, coil voltage, and motor-duty rating to match the complete package-unit nameplate | Packaged units may contain several internal contactors. Replace only the device serving the identified load and match the original control sequence. |
| Commercial split system with multiple compressors | 208–230 V AC or 460–480 V AC | Single-phase or three-phase | One contactor per independently controlled compressor circuit | 24 V AC is common; verify each control circuit | Each compressor’s rated current, locked-rotor current, motor horsepower, and staging sequence | Use individually sized contactors for each compressor unless the equipment manufacturer specifies a common switching arrangement | Do not size one contactor from the total cabinet current unless the wiring diagram and listed equipment ratings permit that arrangement. |
| Electric resistance auxiliary heat or strip heat | 208 V AC or 240 V AC | Single-phase or three-phase | 2 or 3 poles, based on the heater circuit | 24 V AC, 120 V AC, or line-voltage coil depending on the heater controls | Heater kW rating, circuit amperage, number of stages, conductor size, and overcurrent protection | Use a resistive-load-rated contactor with adequate continuous-current capacity and the correct number of poles | Motor-duty ratings alone are not sufficient for electric heat. Confirm the contactor is rated for the intended resistive heating load. |
| Inverter-driven mini-split or variable-speed system | Typically 115 V AC or 208–240 V AC | Single-phase | Often no conventional external compressor contactor | System-specific low-voltage or electronic control | Manufacturer wiring diagram, inverter input current, disconnect requirements, and indoor/outdoor communication wiring | Do not add a standard contactor unless the system documentation specifically permits it | Frequent switching of inverter power can cause faults or damage. Follow the unit’s approved disconnect, control, and service procedures. |
| Fan-only or condenser-fan motor circuit | 115 V AC, 208–230 V AC, or 460–480 V AC | Single-phase or three-phase | 2 poles for many single-phase circuits; 3 poles for three-phase circuits | Control voltage must match the existing circuit | Motor full-load current, locked-rotor current, horsepower, voltage, and starting method | Select a motor-rated contactor based on the fan motor’s voltage, phase, current, and starting duty | Check whether the motor has an integrated overload protector. External overload protection may still be required by the equipment design or local code. |