| Opening location | Identify the wall or barrier containing the opening, its fire-resistance rating, and the opening’s use. | Ask the design professional or authority having jurisdiction (AHJ) which opening-protective rating applies. Requirements depend on the adopted code, occupancy, building design, and location. |
| Required fire rating | Confirm the required duration for the complete shutter assembly, not just the steel curtain. | Common listed fire-protection ratings include 1½, 2, and 3 hours, but these are not interchangeable or universally permitted. Select the rating specified for the actual opening. |
| Applicable building code | Determine the locally adopted building and fire codes, including their edition and amendments. | In the United States, the International Building Code (IBC) addresses opening protectives in Section 716. The applicable requirements and permitted ratings vary by edition and jurisdiction. |
| Fire-test standard | Check the test standard and the product’s fire-test listing or certification. | Relevant U.S. standards can include UL 10B, UL 10C, and NFPA 252. Confirm that the listed assembly and test method are accepted for the project; a wall fire-resistance rating is not automatically the shutter’s required rating. |
| Listing and label | Verify that the complete assembly is listed for the intended application and bears the required permanent label. | Review the label, listing documentation, and installation instructions for the rating, approved components, permitted orientation, and any limitations. |
| Opening size and configuration | Measure the clear opening and confirm width, height, mounting arrangement, and surrounding construction. | Use a configuration covered by the assembly’s listing. Maximum dimensions, guides, barrel, hood, clearances, and supporting construction must match the approved details. |
| Closing and release method | Confirm how the shutter closes during a fire event and how it interfaces with the building’s alarm or detection system. | Depending on the approved design, closure may use an automatic release, fire-alarm interface, or other listed arrangement. Confirm the required operation with the AHJ and follow the product instructions. |
| Smoke control | Determine whether the opening also requires smoke and draft control. | A fire-protection rating alone does not establish smoke-leakage performance. Where required, verify the separate smoke-control listing and applicable test criteria, such as UL 1784. |
| Installation and maintenance | Plan for compliant installation, inspection, testing, and recordkeeping. | NFPA 80 provides requirements for the inspection, testing, and maintenance of fire door assemblies, including applicable rolling steel fire doors. Confirm the edition adopted locally and follow the listed instructions. |